Ep switch
24 Vdc / 24 Vac / 120 Vac
Application & Design
An electro-pneumatic (EP) switch, also known as a three way solenoid valve, is used to electrically open and close a pneumatic
actuated damper. It is wired in series with a normally closed thermostat when used with a fire smoke damper (FSD) to initiate
closure at elevated temperatures. The EP switch can also be used on a smoke damper (SMD) to initiate closure when required in
a smoke control system.
input signal: 24 Vdc
Assembly
(specify) 24 Vac
1
120 Vac
6
3
2
4
7
5
8
item Qty. part # Description
Kit #
1
2
3
-
1
1
1
1
1
1
1
2
1
1
-
-
Valve 1⁄8" NPT
Retaining Clip
9
452460 S/V 120 Vac
380913 S/V 24 Vac
812441
812442
812443
-
381042 S/V 24 Vdc
4
5
6
7
8
651371 Mounting Bracket
380850 2 x 4 x 1.875 Ext. Box
415555 #10 x 0.50 TEK Screw
380257 2 x 4 Blank Cover
415539 #10-32 HH Grounding
Screw (green)
9
1
454850 Label
Kit #s include appropriate voltage solenoid valve shown
under Item 3 and all other Item #s above.
typical setup
Port 3
Exhaust
Solenoid Valve With RRL
TOR/RRL
Wiring
Har dware
ASCO Solenoid
Valve Assembly
Solenoid Valve
Red
RRL
Orange
Red
Black
Port 1
Port 2
Supply
To Actuator
Solenoid Valve With TOR
Solenoid Valve
TOR
Brown
Orange
Black
Blue
Red
Red
Red
Purple
Yellow
Red
Red
Copyright © 2007 Greenheck Fan Corporation
EP Switch Rev. 3 May 2007
|
Groupe SEB USA T FAL Gas Grill CB6080 User Manual
Hafler CD Player IRIS COMPACT DISC PLAYER User Manual
Harman Kardon Stereo Receiver AVR 7000 User Manual
Healthrider Treadmill HRT07921 User Manual
Hoshizaki Ice Maker F 80 I MAH c User Manual
Hotpoint Washer WMYF 822 User Manual
HP Hewlett Packard Computer Monitor A6B85A8ABA User Manual
Humminbird Laminator LCR4 ID User Manual
Husqvarna Lawn Mower 36 EL User Manual
IKEA Refrigerator SF98 User Manual